Batteries level leds.
No 5
No 4
No 3
No 2
No 1
8.2.- Acoustic alarms.
• Discharge. Modulated every 3 seconds with Led (b) active, this indicates that the loads are being supplied from
the batteries, and will be inhibited when the mains returns. See section 8.3 to silence the alarm.
• Low battery. Modulated every 1 second with Led (b) active, it indicates the end of autonomy. The SPS will shortly
block in order to protect the batteries and when the mains returns, the unit will start automatically.
• Overload. Permanent alarm.
• Battery replacement. Permanent alarm with Led (a) alight. Perform the auto-test as in section 7.3.
8.3.- Alarm silencer.
• In "Autonomy mode", Led (b) active on and alarm active, push on the button (6) for less than 1 second to silence
the alarm.
• It is not possible to annul the "Low battery" or "Overload" acoustic alarm.
9.- FAULT LOCALISATION.
• See table 2.
10.- TECHNICAL CHARACTERISTICS.
Input.
Input voltage AC: ................................................................. 100 V, 110 V, 115 V, 120 V, 220 V, 230 V, 240 V ±25 %.
Input frequency: .................................................................. 50 Hz or 60 Hz ±10 % (auto detection).
Output.
Power depending on model: ............................................... See table 3.
Output voltage on inverter: ................................................. 100 V, 110 V, 115 V, 120 V, 220 V, 230 V, 240 V ±5 %.
Inverter working: .................................................................. PWM (Sine-wave).
All manuals and user guides at all-guides.com
Batteries level.
> 91 %
76 - 90 %
51 - 75 %
26 - 50 %
0 - 25 %
Table 1. Batteries level.
- 29 -
Load level leds.
No 5
No 4
No 3
No 2
No 1
Load level.
> 96 %
76 - 95 %
51 - 75 %
26 - 50 %
10 - 25 %