Multi function Input Setting
iF1
00
00 / 06
id1
5
0 / 99 min
iF2
00
00 / 08
id2
5
0 / 99 min
LGS
MAn
no, MAn, dor
SbE
YES
no, YES
FF
00
00 / 02
Fd
5
0 / 99 min
Fr
-5
-40 / 70 °C
FS
-2
-12 / 0 °C
Fh
2
1 / 12 °C
FdS
no
no, YES
This document is subject to change without notice
Description
Digital input 1 selector:
nd
00 = Not used
04 = 2
setpoint
01 = Interlock alarm
05 = Standby
02 = Alarm report
06 = Fan only mode
03 = Door
Digital input 1 delay (alarms, door)
Digital input 2 selector:
00 = Not used
05
= Standby
01 = Interlock alarm
06
= Fan only mode
02 = Alarm report
07 - 08 = Defrost start
03 = Door
nd
04 = 2
setpoint
Digital input 2 delay (alarms, door)
Light switch command:
not used, manual, door opened
Standby key enable
Fan Setting
Fan operation selector:
00 = Parallel to
01 = Always On
compressor
02 = On-off control
Fan start up delay
Fan start up temperature
On-off control delta (with return air temperature)
On-off control hysteresis
Fan enable at door opened
Code
Default
SF1
3
SF2
3
So1
0
no
SE2
(YES*)
So2
0
Sh2
0
SE3
no
So3
0
command
Sd
t1
Pu
3
AA1
LGt
AA2
(only
AL1
ER55)
Add
255
MM
-
hh
-
dAY
-
bio
0
biS
0
biE
0
* Default values of Mod = 02 (negative temperature)
IS_ER54 ER55_24-85737-1358 Rev. A
Range
Description
Probe Setting
0 / 10 min
Compressor On time at sensor failure
0 / 10 min
Compressor Off time at sensor failure
-12 / 12 °C
Sensor T1 offset
no, YES
Sensor T2 enable
-12 / 12 °C
Sensor T2 offset
0 / 100%
Sensor T2 weight
Sensor T3 selector:
no, dSc, 2ev
not used, discharge air, 2
-12 / 12 °C
Sensor T3 offset
Display Setting
t1, t2, t3
Displayed sensor
0 / 100
Display refreshing time
Auxiliary Output Setting
no, AL0, AL1,
Auxiliary output 1 and 2 selectors
LGt, dEF, Pdn
no: not used
AL0 = Alarm at
no, AL0, AL1,
LGt, dEF
opening
AL1 = Alarm at closing
Address & Clock
1 / 255
Network address
0 / 59 min
Clock minutes
0 / 23 hours
Clock hours
1 / 7
Clock day of the week (1: Monday ....7: Sunday)
nd
2
Setpoint Setting
nd
-12 / 12 °C
Bias 2
setpoint
nd
0 / 23.5 hours
2
setpoint scheduler, start event
nd
0 / 23.5 hours
2
setpoint scheduler, stop event
nd
evaporator
LGt = Light command
nd
dEF = 2
evaporator
defrost
Pdn = Pump down