Sime RONDO 3 OF Instrucciones De Instalación Y Mantenimiento página 41

Ocultar thumbs Ver también para RONDO 3 OF:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 13
tenance is carried out.
3.3.1
Smoke side boiler (fig. 8)
To carry out cleaning of the smoke pas-
sages remove the screws that fix the door
to the body of the boiler and with the special
cleaning brush clean the internal surfaces
and the smoke evacuation tube well, remov-
ing any deposits.
Once the maintenance is compled, the
baffles have to be fitted onto the original
positions (ref. RONDÒ/ESTELLE 3-4-5-6 OF
models).
In the ESTELLE versions the maintenance
operations can be carried out without
removing the burner.
3.3.3
Disassembly of the casing
To disassemble the casing of the boiler, pro-
ceed as follows (fig. 10):
– remove the cover (12) fixed with pin
clutches;
– remove the panel (8) which are fixed to
the sides by pin clutches;
– remove the control panel (9) whose sides
are fixed by four self-tapping screws;
– remove the back panels (6) and (7) which
are fixed to the sides by ten self-tapping
screws;
– disassemble the left side (3) unscrewing
the screws fixing it to the upper bracket
(5), and remove the screws that fix it to
the lower bracket (1);
– disassemble the right side (4) following
the same operations.
3.3.4
Fault finding
Herefater we outline a number of potential
problems that may occur on the appliance
and the relevant list of actions required. A
working fault, in most cases, provocates the
"lock out" signal onto the control panel of
the control box.
When this light turns on, the burner can
operate again only after the reset button
has been pressed; if this has been done
and a regular ignition occurs, it means the
failure can be defined momentary and not
dangerous. On the contrary, if the "lock out"
stays, the cause of the fault, as well as the
relevant action must be made according to
the following chart:
The burner does not ignite
– Check the electric connections.
– Check the regular fuel flow, the clean-
ness of the filters, of the nozzle and air
vent from the tube.
– Check the regular spark ignition and the
proper function of the burner.
The burner ignites regularly but the flame
goes out immediately
– Check the flame detection, the air cali-
bration and the function of the appliance.
Difficulty in regulating the burner and/or
lack of yield
– Check: the regular flow of fuel, the clean-
ness of the boiler, the non obstruction of
the smoke duct, the real input supplied by
the burner and its cleanness (dust).
The boiler gets dirty easily
– Check the burner regulator (smoke anal-
ysis), the fuel quantity, the flue obstruc-
tion and the cleanness of the air duct of
the burner (dust).
The boiler does not heat up
– Control the cleanness of the shell, the
matching, the adjustment, the burner
performances, the pre-adjusted temper-
ature, the correct function and position of
the regulation stat.
– Make sure that the boiler is sufficiently
powerful for the appliance.
Smell of unburnt products
– Control the cleanness of the boiler shell
RONDO' 3/4 OF
ESTELLE 3/4 OF
RONDO' 5/6 OF
ESTELLE 5/6 OF
Fig. 8
41