CAUTION
After con rmation of the above conditions, follow these guidelines when performing wiring:
Always have an individual power circuit speci cally for the air conditioner. Always follow
the circuit diagram posted on the inside of the control cover.
Screws fastening the wiring in the casing of electrical ttings may come loose during
transporation. Because loose screws may cause wire burn-ou, check that the screws are
tightly fastened.
• Check the speci cations for the power source.
• Con rm that electrical capacity is su cient.
Con rm that starting voltage is maintained at more than 90 percent of the rated voltage
marked on the name plate.
• Con rm that the cable thickness is as speci ed in the power source speci cations.
• Always install an earth leakage circuit breaker in wet or moist areas.
The following can be caused by a drop in voltage: vibration of a magnetic switch,
damaging the contact point, broken fuses, and disturbance of normal functioning.
Disconnection from a power supply must be incorporated into the xed wiring. It must
have an air gap contact separation of at least 3mm in each active (phase) conductors.
• Before accessing terminals, all supply circuits must be disconnected.
NOTE:
To satisfy the EMC compulsory regulations, which is required by the international standard
CISPR 14-1:2005/A2:2011 in speci c countries or districts ,please make sure you apply the
correct magnetic rings on your equipment according to the wiring diagram that adhere to
the your equipment .
Please contact your distributor or installer to get further information and purchase
magnetic rings (The supplier of magnetic ring is TDK(model ZCAT3035-1330)or similar) .