Amount of refrigerant
Installation height
to be charged (kg)
(m)
1.0
1.05
1.1
1.15
1.2
1.25
1.3
1.35
1.4
1.45
1.5
1.55
1.6
1.65
1.7
1.75
1.8
1.85
1.9
Reusable mechanical connectors and ared joints are not allowed indoors.
(EN Standard Requirements).
Mechanical connectors used indoors shall have a rate of not more than 3g/year at 25% of the
maximum allowable pressure. When mechanical connectors are reused indoors, sealing parts shall
be renewed. When ared joints are reused indoors, the are part shall be re-fabricated.
(UL Standard Requirements)
When mechanical connectors are reused indoors, sealing parts shall be renewed. When ared
joints are reused indoors, the are part shall be re-fabricated. (IEC Standard Requirements)
Mechanical connectors used indoors shall comply with ISO 14903.
European Disposal Guidelines
This marking shown on the product or its literature, indicates that waste electrical and
eletrical equipment should not be mixed with general household waste.
This appliance contains refrigerant and other potentially hazardous materials. When disposing of
this appliance, the law requires special collection and treatment. Do not dispose of this product as
household waste or unsorted municipal waste.
When disposing of this appliance, you have the following options:
• Dispose of the appliance at designated municipal electronic waste collection facility.
• When buying a new appliance, the retailer will take back the old appliance free of charge.
• The manufacturer will take back the old appliance free of charge.
• Sell the appliance to certi ed scrap metal dealers.
Special notice
Disposing of this appliance in the forest or other natural surroundings endangers your health and is bad
for the environment. Hazardous substances may leak into the ground water and enter the food chain.
Minimum room
area (m²)
0.6 /1.8 /2.2
9 /1 /1
0.6 /1.8 /2.2
9.5 /1.5 /1
0.6 /1.8 /2.2
10.5 /1.5 /1
0.6 /1.8 /2.2
11.5 /1.5 /1
0.6 /1.8 /2.2
12.5 /1.5 /1
0.6 /1.8 /2.2
13.5 /1.5 /1
0.6 /1.8 /2.2
14.5 /2 /1.5
0.6 /1.8 /2.2
16 /2 /1.5
0.6 /1.8 /2.2
17/2 /1.5
0.6 /1.8 /2.2
18 /2 /1.5
0.6 /1.8 /2.2
19.5 /2.5 /1.5
0.6 /1.8 /2.2
21 /2.5 /2
0.6 /1.8 /2.2
22 /2.5 /2
0.6 /1.8 /2.2
23.5 /3 /2
0.6 /1.8 /2.2
25 /3 /2
0.6 /1.8 /2.2
26.5 /3 /2
0.6 /1.8 /2.2
28 /3.5 /2.5
0.6 /1.8 /2.2
29.5 /3.5 /2.5
0.6 /1.8 /2.2
31/3.5 /2.5
(Waste Electrical & Electronic Equipment)
Amount of refrigerant
Installation height
to be charged (kg)
(m)
1.95
0.6 /1.8 /2.2
2.0
0.6 /1.8 /2.2
2.05
0.6 /1.8 /2.2
2.1
0.6 /1.8 /2.2
2.15
0.6 /1.8 /2.2
2.2
0.6 /1.8 /2.2
2.25
0.6 /1.8 /2.2
2.3
0.6 /1.8 /2.2
2.35
0.6 /1.8 /2.2
2.4
0.6 /1.8 /2.2
2.45
0.6 /1.8 /2.2
2.5
0.6 /1.8 /2.2
2.55
0.6 /1.8 /2.2
2.6
0.6 /1.8 /2.2
2.65
0.6 /1.8 /2.2
2.7
0.6 /1.8 /2.2
2.75
0.6 /1.8 /2.2
2.8
0.6 /1.8 /2.2
2.85
0.6 /1.8 /2.2
Correct Disposal of This Product
Minimum room
area (m²)
33 /4 /2.5
34.5 /4 /3
36 /4 /3
38 /4.5 /3
40 /4.5 /3
41.5 /5 /3.5
43.5 /5 /3.5
45.5/5 /3.5
47.5/5.5 /4
49.5 /5.5 /4
51.5 /6 /4
54 /6 /4
56 /6.5 /4.5
58 /6.5 /4.5
60.5/7 /4.5
63 /7 /5
65 /7.5 /5
67.5 /7.5 /5
70 /8 /5.5