• "During the UL evaluation, only Risk of Electrical Shock and Risk of Fire aspects were
investigated. Functional Safety aspects were not evaluated"
• In order to comply with CSA C22.2 No. 14-2010 (cUL) following external Input Chokes
need to be installed: See table 1 below!
Table 1: Mains input chokes for CSA applications:
Cat. No. Housing
13G6
B, C
14G6
C
15G6
C
Branch Circuit Protection for G6 - C Drive series
I) Fuses:
Cat. No.
Housing
13G6
B, C
14G6
15G6
The voltage rating of the external fuses shall be at least equal to the input voltage of the dri-
ves.
II) Listed (DIVQ, DIVQ7/CSA Certified ) Circuit Breakers, Type, manufacturer and electrical
ratings as specified below:
Cat. No. Housing
13G6
B or C
14G6
C
15G6
C
III) Listed (NKHJ, NKHJ7/CSA Certified) Type E Self Protected Manual Motor Controllers,
Type and manufacturer and electrical ratings as specified below:
Cat.
Housing Self Protected Ma-
No.
13G6
B, C
14G6
C
15G6
C
Input Voltage [V]
480 / 3ph
480 / 3ph
480 / 3ph
Input Voltage
[ V ]
480 / 3ph
C
480 / 3ph
C
480 / 3ph
Type
5SJ4 320-8HG42
S203UP-K 20
FAZ D20/3-NA
1489 A3D 200
5SJ4 325-8HG42
S203UP-K 25
FAZ D25/3-NA
1489 A3D 250
N/A
nual Motor Cont-
roller,
Type
PKZM0(1) 25-E
PKZM0(1) 25-E
PKZM0(1) 32-E
Reactor Cat. No.
13DRB08–1851
14DRB08–1451
15DRB08–9841
UL248 Fuse rating 600V [A]
Manufacturer
SIEMENS
ABB
Eaton
Allen Bradley
SIEMENS
ABB
Eaton
Allen Bradley
N/A
Manufac-
Self Protected
turer
Manual Motor
Eaton
480Y/277V, 15.0 Hp
Eaton
480Y/277V, 15.0 Hp
Eaton
480Y/277V, 20.0 Hp
Anexo
FLA
Inductance [mH]
3 x 16A
1.83
3 x 20A
1.47
3 x 30A
0.98
Class CC, J or RK5
20
25
40
Ratings
480Y/277V, 20A
480Y/277V, 25A
N/A
Dial setting
Controller,
ratings
[ A ]
25
25
32
E - 25