14 – TROUBLESHOOTING
Symptoms
The gate does not
correspond to the
travel where it has
been installed (It
brakes before the
closing stopper or
slams when closing).
Gate remains open
and when it receives a
command for opening,
it closes.
'SN' LED quickly
flashing and the motor
shuts off.
To install digital systems such as encoders, photocells, among
others, it is recommended that the network piping electrical or
connecting cables be separated from the engine to avoid possible
eletronic noise.
Probable Cause(s)
There is a memorized
travel different from
the travel of the place
where it has been
installed.
Acquiring
(Memorization) hasn't
been performed
properly.
Current sensor
activated. This might
happen when there
is a problem with the
motor.
WARNING
Action(s)
Press both 'CMD'
buttons at the same
time and hold them
pressed until the 'SN'
LED lights.
Refer to item 3.1
First activation after
installation (Acquiring /
Self-learning).
Check the resistor of
the stator. Check the
motor current (it must
be less than 3A RMS
(Average) and 5A RMS
(peak) (Maximum 2
seconds)).