OPERATING ISSUE
Turntable is malfunctioning.
PAGE 5 OF 15
TROUBLESHOOTING CONTINUED
CAUSES
It is not set high enough.
It is not functioning properly.
The frequency drive is not functioning (i.e. no
faults displayed).
The frequency drive is not connected properly
to the motor.
Locate the turntable speed potentiometer dial on the AC
frequency drive.
Adjust potentiometer towards 100% to set speed.
Step on the foot switch, and use a voltmeter to test for
continuity of the foot switch.
Tighten wiring, replace the foot switch if necessary.
Remove power to the drive. Wait sixty seconds, and
supply power back.
Refer to frequency drive manufacturer's manual for
specific fault.
Locate the turntable motor, and use a voltmeter to check
continuity of all motor wires.
Tighten or replace wiring as necessary.
Replace the turntable frequency drive.