EN
Firmly grasp the insulated grip of the Tester
probe L2, it is better for the sensitivity of the phase
rotation test.
8. RCD Voltage Test
Voltage Test with RCD Trip Test
During voltage tests in systems equipped with RCD
circuit breakers, a RCD switch can be tripped at a
nominal residual current of 10mA or 30mA by
measuring the voltage between L and PE.
This Tester is equipped with an internal load
enabling the tripping of an RCD protection device of
10mA or 30mA.
To avoid RCD tripping, a test has to be carried out
between L and N during approx. 5sec. Immediately
afterwards, voltage testing between L and PE can be
carried out without RCD tripping.
8