2.3 Do not install the machine in places with strong wind or dust;
2.4 Do not install the machine where it is often passed through the air suction side and air
exhaust side;
2.5 The installation position of the machine should be adequately drained to the nearby sewer.
Heat Pump Installation Space Diagram
Note
Installation in the following locations may cause the machine to malfunction:
1. A place with more oil;
2. Wet place
3. Seaside saline-alkali area;
4. Special environmental conditions;
5. High-frequency facilities such as wireless equipment, welding machines, and medical equipment.
3. Outdoor Unit Specific Installation Steps
3.1
Install the unit on a solid surface such as concrete, and the load-bearing cover or mounting
bracket must meet the strength requirements;
3.2
Fasten the outdoor unit to the mounting bracket with bolts and nuts and keep it level;
3.3
If installed on a wall or a roof, the bracket must be firmly fixed to prevent damage caused by
an earthquake or strong wind;
3.4
The positioning dimension of the outdoor unit installation base is 810*394mm. It is required
to install four-position foot bolts with a diameter of 10mm—at the bottom of the installation
of the outdoor unit. The inch recommendation is 1200*450mm.