REFRIGERANT PIPING
• If refrigerant gas leaks during the installation work, ventilate the room immediately.
• If the leaked refrigerant comes in contact with fire, noxious gas may generate.
• After the installation work, confirm that refrigerant does not leak.
• If refrigerant gas leaks into the room and flows near to a source of fire, noxious gas maybe generated.
When using long lengths of refrigerant piping. Provide support brackets at intervals of 2.5 m to 3 m.
If the pipes are not fixed abnormal sounds maybe generated.
Ensure the supplied R410A flare nuts are used.
Permissible pipe length and permissible height difference
This differs depending on the outdoor units. For details, refer to the Installation Manual supplied with the outdoor
unit.
Piping material and dimensions
Piping material
Indoor unit capacity type
Gas side
Pipe size (mm)
Liquid side
• Use new and clean pipe, ensuring that the pipes are not contaminated with dust, oil, moisture, etc.
Pipe flaring
Flaring
1. Cut the pipe with a pipe cutter.
OK
Obliquity
90˚
2. Place flare nut onto the pipe, and flare the pipe.
(Use the flare nut fitted to the unit or one that is
R410A compatible)
As the flaring sizes of R410A differ from that used
on R22. It is recommended to use a dedicated
R410A flaring tool. However a conventional flare
tool can be used, by adjustment of the projection of
the copper pipe.
All manuals and user guides at all-guides.com
WARNING
REQUIREMENT
Phosphor deoxidization seamless pipe for air conditioner
MMU-
0071 to 0121 type
Ø9.5
Ø6.4
NO GOOD
Roughness
Warp
12
0151 to 0181 type
• Flaring diam. meter size :
A (Unit : mm)
Outer diam. of copper pipe
6.4
9.5
12.7
15.9
In case of flaring for R410A with the conventional
*
flare tool, make a margin of 0.5 mm longer than that
of R22 pipe so that the flare size matches with the
specified size.
The copper pipe gauge is useful for adjusting the
projection margin size.
Ø12.7
Ø6.4
A
A
+0
- 0.4
R410A
9.1
13.2
16.6
19.7