Descargar Imprimir esta página

Toshiba MMU-AP0071MH Manual De Instalación página 24

Ocultar thumbs Ver también para MMU-AP0071MH:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

8
TEST RUN
Before test operation
• Before turning on the power supply, carry out the following
procedures.
1) Using 500V-megger, check there is 1MΩ or more between the
terminal block of the power supply and the earth.
If 1MΩ or less is detected, do not run the unit.
2) Check that all the valves of the outdoor unit are fully opened.
• Never push the electromagnetic contactor to carry out a forced test operation.
(It is very dangerous because a protective device does not work.)
How to execute test operation
• To carry out a fan operation in a single indoor unit, firstly turn off the power supply to the unit. Then short CN72
found on the P.C. board. Once completed turn the power to the unit back on and start the unit in FAN only mode.
Upon completion of the test do not forget to remove the short circuit on CN72.
• Using the remote controller, check the unit is in normal operation. For the operation procedure, refer to the
supplied Owner's Manual. A forced test operation can be executed in the following procedure under the condition
of thermo.-OFF of room temperature.
In order to prevent the test operation from running continuously, the operation will cease after a period of
60 minutes. The unit will then return back to its original operation.
NOTE
Do not use a forced operation in cases other
than test operation because it applies an
excessive load onto the air conditioner.
In case of wired remote controller
Procedure
TEST
Keep the
button pushed down for 4 seconds or more.
1
[TEST] is displayed on the display part and the selection of the test mode is
permitted.
2
ON / OFF
Push
MODE
Using
button, select the operation mode, [COOL] or [HEAT].
• Do not run the air conditioner in a mode other than [COOL] or [HEAT].
3
• The temperature controlling function will not work during the test operation.
• Fault detection will perform as usual.
After the test operation, push the
4
(Display part is the same as procedure
TEST
Push the
button to cancel (release from) the test operation mode.
5
([TEST] disappears on the display part and the status returns to a normal.)
All manuals and user guides at all-guides.com
button.
ON / OFF
button to stop the operation.
1
)
To protect the compressor at
startup. Ensure the power supply
is left on for 12 or more hours
before operation.
TEMP.
TIMER SET
TIME
FILTER
RESET TEST
SET CL
1, 5
Description
21
WARNING
ON / OFF
2, 4
FAN
MODE
3
SWING/FIX
VENT
UNIT
TEST

Publicidad

loading

Este manual también es adecuado para:

Mmu-ap0091mhMmu-ap0121mhMmu-ap0151mhMmu-ap0181mh