INPUT REGISTERS (Read only)
Modbus Adress
30006
Defrost status
30026
Extract air temperature
30027
Exhaust air temperature
30026
Outdoor air temperature
30026
Supply air temperature
30030
Relative humidity extract air
30031
Relative humidity exhaust air
30032
Relative humidity outdoor air
30033
Relative humidity supply air
Control voltage extract
30060
30061
Control voltage supply motor
30062
RPM extract motor
30063
RPM supply motor
30064
Bypass damper position
30091
Actual working mode
HOLDING REGISTERS (Read/Write)
Modbus Adress
40001
Modbus slave adress
40002
40003
Modbus parity
40049
40050
40051
40052
40053
40054
40057
Manual by-pass timer
40064
Min ODA for by-pass
40066
Min ETA for by-pass
Register
Values
-500...+600 dºC
-500...+600 dºC
-500...+600 dºC
-500...+600 dºC
0-100%
0-100%
0-100%
0-100%
0-100
motor
0-100
0-5000 rpm
0-5000 rpm
Register
Values
1-247
Baudrate
Day
1-31
Month
1-12
Year
2016-2100
Hour
0-23
Minutes
0-59
Seconds
0-59
1-8 h
120...200 dºC
210-300 dºC
Description
0
Not active
1
Active (fireplace defrost)
2
Active (with pre-heater)
Active (unbalanced
3
airflows)
dºC
dºC
dºC
dºC
%
%
%
%
dV
dV
rpm
rpm
0
Closed
1
Open
2
Error
0
Snooze mode
1
Low speed
2
Medium speed
3
High speed
4
Boost
Auto mode (humidity
5
sensor)
6
Auto mode (VOC sensor)
Auto mode (0-10V
7
control)
8
Boost in auto mode
9
Weekly program 1
10
Weekly program 2
11
Weekly program 3
12
Weekly program 4
Description
48
4800
96
9600
192
19200
384
38400
0
EVEN
1
ODD
2
No parity (2 stop bits)
Day (clock)
Month (clock)
Year (clock)
Hour (Clock)
Minutes (Clock)
Seconds (Clock)
Manual by-pass timer
Minimum outdoor
temperature for by-pass
activation
Minimum extract
temperature for by-pass
activation
Default
Data type
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
16 bit word
Default
Data type
1
16 bit word
16 bit word
16 bit word
192
16 bit word
16 bit word
16 bit word
0
16 bit word
16 bit word
Set from factory
16 bit word
Set from factory
16 bit word
Set from factory
16 bit word
Set from factory
16 bit word
Set from factory
16 bit word
Set from factory
16 bit word
8 h
16 bit word
130 dºC
16 bit word
230 dºC
16 bit word
31