Password-protected menus
40031
30
40032
31
n/a
n/a
6
Password-protected menus
6.1
Overview
Password-protected menus allow the preset values to be adapted as required:
To change the dimensions from mm to inches or vice versa
To change from volume flow to flow rate measurement
To change between system units l/m3 or Impgal/USgal
To change between flow units l/s, l/min or gal/s, gal/min or USgals/s, USgals/min
To change the current output parameters
To change the pulse output parameters
To change the Modbus output parameters (if installed)
To change the calibration parameters
To change the totalizer settings
NOTICE
The password for the password-protected area is: 71360.
6.2
Opening a password-protected menu
Signal strength and the present flow are displayed:
► Press the button.
You are prompted for the password.
If the password is not entered, the display automatically changes back to the flow value after a few sec-
onds.
► Enter the password (71360).
See Section Changing the numerical values in data menus.
► Make all the desired changes.
► Press the button.
The current parameter is skipped.
► Press the button User Menu: Exit.
The new values are stored and the password-protected menu is closed.
26
0x42
0xc8
iee754
Instrument ATA
0x00
0x00
0xed
Int-16
CRC-16
0x98
Sig: 98%
4-20mA
0260.8
PULSE
Diagnostic Data
Units in nanoseconds
-
!
1/min
User Manual