Leakage from the drain
valve
Water delivered with
unpleasant smell/taste
Coarse material in filtered
water
Water leakage from the
system
A4 DISPOSAL
Dispose of separately from other waste. Hand in the end-of-life device at a suitable segregated waste collection
centre. Before disposing of the waste and in the event of any doubts, contact your local waste management
service for clarification.
A5 MARKING
See the Technical diagrams and data sheet.
A6 PARTS SUBJECT TO WEAR
Filter cartridge, O-ring.
ASSEMBLY AND INSTALLATION MANUAL
B1 INSTALLATION
B1.1 Prior to installation
BravoFIL is delivered in packaging that provides adequate protection from external contamination. Transport
and store the equipment in its original, unopened packaging. During transport and storage, the equipment
should not be exposed to temperatures below 5°C or above 40°C. In the event of very heavy shocks during
transport or assembly, do not install the equipment but replace it, even if there is no obvious damage to the
plastic parts. To avoid external contamination, always keep the filter closed in its original box and remove it
only immediately prior to installation. After opening the box, check the integrity of the equipment and the
presence of all the supplied items. If in doubt, refrain from using it and contact the supplier. Use only original
replacement parts.
Warning! BravoFIL is not supplied as standard with anti-flooding devices or devices for monitoring,
detecting and signalling uncontrolled water leakage. If necessary, provide a suitable anti-flooding
device separately.
Install only in rooms with a floor drain to prevent damage caused by accidental water spillage.
In older buildings, check whether the metal water pipe is used for grounding the electrical system (a bridged
connection on the water meter is a clear indication of this). Check for other grounding devices before opening
the pipe.
Acqua Brevetti SRL disclaims any liability for damage to property or persons resulting from incorrect installation
of the equipment and/or installation in a system not in compliance with the current laws or where the
requirements of this manual have not been met.
Excessive flow rate through the
filter
Low input pressure
Drain valve not fully closed due to
a foreign body lodged in the
housing.
Filter unaligned
Contaminated supply water
Prolonged disuse (stagnation)
High concentration of coarse
material in the incoming water
Damaged or improperly
positioned cartridge
Bowl not closed properly.
Badly positioned or damaged O-
ring.
Reduce the flow rate delivered by
the filter.
Increase the supply pressure.
Contact a TSC.
Contact a TSC.
Check the pre-filtered water
characteristics
Flush several times while allowing
the filter to drain for a few minutes.
If necessary, replace the filter
cartridge. Contact a TSC.
Check the pre-filtered water
characteristics
Check the cartridge. Replace if
necessary. Contact a TSC.
Tighten the bowl thoroughly.
Check the O-ring seal. Replace if
necessary. Contact a TSC.