2.0 - TECHNICAL DATA
• Use
• Ambient temperature (TS)
• Power voltages (see table 2)
• Power supply tolerance
• Electric wiring
• Absorbed power
• Maximum operating pressure
• Closing time
• Protection rating
• Mechanical resistance
• Rp threaded connections
• NPT threaded connections
• In compliance with
* Only single-phase, the device does not work if powered with three-phase
3.0 - COMMISSIONING THE DEVICE
3.1 - OPERATIONS PRIOR TO INSTALLATION
• It is necessary to close the gas upstream of the valve prior to installation;
• Make sure that the line pressure DOES NOT EXCEED the maximum pressure declared on the product label;
• Any protective caps (if any) must be removed prior to installation;
• Valve pipes and insides must be clear of any foreign bodies;
• Make sure that the pipe thread is not too long, to prevent damaging the body of the device when screwing it on;
• The safety regulations on handling loads in force in the country of installation must be complied with. If the device to
be installed exceeds the weight allowed, suitable mechanical equipment and adequate slings must be used. Necessary
precautions must be taken during the handling phases so as not to damage/ruin the external surface of the device.
• In accordance with EN 161 a suitable filter must be installed upstream of a gas closing safety device;
• With outdoor installation, it is advisable to provide a protective roof to prevent rain from damaging the electrical parts of
the device.
• Prior to carrying out any electrical wiring operations, make sure that the main voltage matches the supply voltage indicated
on the product label;
• Cut out power prior to proceeding with wiring;
• According to the plant geometry, check the risk of explosive mixture arising inside the piping;
• If the solenoid valve is installed near other devices or as part of an assembly, compatibility between the solenoid
valve and this other device must be evaluated beforehand.
•Avoid installing the solenoid valve near surfaces that could be damaged by the coil temperature;
•Provide a protection against impacts or accidental contacts if the solenoid valve is accessible to unqualified
personnel.
Madas Technical Manual - 3|3.5 - REV. 0 of 10
: non-aggressive gases of the three families (dry gases)
: -15 ÷ +60 °C
: 12 Vdc - 12 V/50 Hz - 24 Vdc - 24 V/50 Hz - 110 V/50-60 Hz - 230 V/50-60 Hz*
: -15% ... +10%
: cable gland M20x1,5
: see table 2
: 500 mbar
: < 1 s
: IP65
: Group 2 (according to EN 13611)
: (DN 15 - DN 20) according to EN 10226
: on request
: EMC Directive 2014/30/EU - LVD Directive 2014/35/EU
RoHS II Directive 2011/65/EU
9
Oct 2018
th
voltage.
MP16/RM N.A.