Descargar Imprimir esta página

Toshiba RAV-HM561UT-E Manual De Instalación página 63

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 23
 To find an indoor unit's position from its address
1
Push and hold menu button and [
] setting button simultaneously for 10 seconds or more.
E.g.) A unit number 1-1 is indicated on the LCD of the remote controller. The indicated number shows the line
(system) address and indoor unit address of the unit.
2
When 2 or more indoor units are connected to the remote controller (group-controlled units), a number of other
connected units appears each time you push the [
3
Push the ON/OFF button, return to the normal mode.
123-EN
] [
] buttons.
9
Test run
 Before test run
• Before turning on the power supply, carry out the
following procedure.
1) By using 500 V-megger, check that resistance
of 1 MΩ or more exists between the terminal
block 1 to 3 and the earth (grounding work).
If resistance of less than 1 MΩ is detected, do
not run the unit.
2) Check the valve of the outdoor unit being
opened fully.
• To protect the compressor at activation time, leave
power-ON for 12 hours or more before operating.
 Execute a test run
Operate the unit with the wired remote controller as
usual.
For the procedure of the operation, refer to the
attached Owner's Manual.
A forced test run can be executed in the following
procedure even if the operation stops by thermostat-
OFF.
In order to prevent a serial operation, the forced test
run is released after 60 minutes have passed and
returns to the usual operation.
CAUTION
CAUTION
Do not use the forced test run for cases other than the
test run because it applies an excessive load to the
devices.
– 62 –
Wired remote controller
Be sure to stop the air conditioner before making
settings.
(Change the setup while the air conditioner is not working.)
4
3
3
1
2
1
Push and hold OFF timer button and [
setting button simultaneously for 10
seconds or more. [TEST] is displayed on the
display part and the test run is permitted.
2
Push ON/OFF button.
3
Push menu button to select the operation
mode. Select [
Cool] or [
Heat] with
[
] [
] setting button.
• Do not run the air conditioner in a mode other
than [Cool] or [Heat].
• The temperature setting function does not work
during test run.
• The check code is displayed as usual.
4
After the test run, push OFF timer button to
stop a test run.
([TEST] disappears on the display and the air
conditioner enters the normal stop mode.)
]
124-EN

Publicidad

loading

Este manual también es adecuado para: