Bond in accordance with national and
local codes. Open bonding lugs are
located at the top of the junction box.
120/240 VAC Source
N
L1
120 V
120 V
Neutral Bus
(In Breaker Box)
3. Make Electrical Connections
NOTE: The product model number is printed on a label on the blower side of the bath. This label also
identifies the electrical rating of the product. All baths come equipped with a wiring junction box and
are designed to operate between 220 V and 240 V at either 50 Hz or 60 Hz.
WARNING: Risk of electric shock. Disconnect the power before performing the following
procedures.
WARNING: Risk of electric shock. Connect the blower to a properly grounded Ground-Fault
Circuit-Interrupter (GFCI) or Residual Current Device (RCD). This will provide additional
protection against line-to-ground shock hazard. A 220-240 V, 20 A, 50/60 Hz dedicated circuit is
required.
IMPORTANT! The load neutral is not used. There should be no connection to the load neutral terminal
on the Ground-Fault Circuit-Interrupter (GFCI) breaker. The green wire with the yellow stripe is the
equipment ground and needs to be connected to the neutral bus in the main circuit breaker box.
NOTE: The wiring harness includes an antenna for the optional remote control. Do not alter or damage
this antenna during installation.
Connect service to the junction box. The junction box contains blue, brown, and green with a yellow
stripe colored wires and a ground lug.
Follow local electrical codes. Bond in accordance with national and local codes.
Kohler Co.
L2
Breaker Box
Typical Two-Pole
Circuit Breaker
with GFCI
240 V
* Line Neutral
(White
Curly Wire)
* Equipment Ground
Control
Typical Wiring Connection for North America
* Connections to be Made
at the Circuit Breaker
*L2
240 V
*L1
No Connection
(Load Neutral)
Field Wiring
(From Junction Box
to GFCI Breaker)
7
Blower Motor Cord
External Power
Wire Connector
Control Power
Junction Box
Blue (L1)
Electrician to provide
suitable strain relief.
Control
Power Supply
Ground
(Green with
Yellow Stripes)
From Control
Brown (L2)
Wire Connectors
1199249-2-D