NORMAL OPERATION / FLAME DETECTION TIME
The control box has a further function to guarantee the correct burner operation (signal: GREEN LED permanently on).
To use this function, wait at least ten seconds from the burner ignition and then press the control box button for a minimum of 3 seconds.
After releasing the button, the GREEN LED starts flashing as shown in the figure below.
GREEN LED on
wait at least 10s
The pulses of the LED constitute a signal spaced by approximately 3 seconds.
The number of pulses will measure the probe DETECTION TIME since the opening of gas valves, according to the following table:
SIGNAL
1 blink
2 blinks
6 blinks
KIT INTERFACE ADAPTER RMG TO PC Code 3002719
ACCESSORIES
(optional):
• RADIO DISTURBANCEPROTECTION KIT
If the burner is installed in places particularly subject to radio disturbance (emission of signals exceeding 10 V/m) owing to the presence of an
INVERTER, or in applications where the length of the thermostat connections exceeds 20 metres, a protection kit is available as an interface
between the control box and the burner.
BURNER
• KIT FOR LPG OPERATION: The kit allows the RS 64 MZ burner to operate on LPG.
Output kW
Blast tube lenght mm
• KIT LONG HEAD
• CLEAN CONTACTS KIT
• GROUND FAULT INTERRUPTER
• KIT INTERFACE ADAPTER RMG TO PC
• GAS TRAINS TO COUPLE WITH THE BURNER, ACCORDING TO REGULATION EN 676 (with valves, pressure governor and filter): see
page 8.
NOTE: The installer is responsible for the addition of any safety device not foreseen in this manual.
Press button
for > 3s
FLAME DETECTION TIME
0.4s
0.8s
2.8s
Code 3010434
18
Interval
signal
3s
This is updated in every burner start-up.
Once read, the burner repeats the start-up cycle by briefly
pressing the control box button.
WARNING
If the result is > 2s, ignition will be retarded.
Check the adjustment of the hydraulic brake of the gas
valve, the air damper and the combustion head adjustment.
RS 64 MZ
Code 3010386
400 - 920
250
385
Code 3010435
Code 3010427
Code 3010419
Code 3010321
Code 3002719
signal