transmitter.
5= NEGATIVE, 6= POSITIVE.
6-7
(Photocell RX) 24 Vdc output, max. 15 W, for POWER SUPPLY OF RX AND POSSIBLE OTHER TX ELEMENTS OF PHOTOCELLS, EXTERNAL
RECEIVERS etc; connect max. 3 pairs of photocells. 6= POSITIVE, 7= NEGATIVE.
8-9
(Flashing light) 24 Vdc FLASHING LIGHT output (max. 15 W). The signal supplied is already specially modulated for direct use. The flash-
ing frequency doubles during the closing phase. 8= POSITIVE, 9= NEGATIVE.
10-11 (Antenna) AERIAL input for built-in RX 433,92 MHz. 10= EARTH, 11= SIGNAL.
M4
quick connector for ENCODER and MOTOR connection. Brown = 5 Vdc (+5V), green = ENCODER SIGNAL (ENC), White = 0 Vdc (GND),
black = MOTOR NEGATIVE, red = MOTOR POSITIVE.
17 - 18
24V – 1.2Ah BATTERY input.
3.4 Memorisation procedure
I
MPORTANT: After powering up the control panel, wait for 2 seconds before starting the adjustment procedures.
Once you have finished installing the automation system:
To program section doors use the ENTER button. To program up-and-over doors use the O/C button.
1_ hold the ENTER (O/C) key on the board down for 3 sec. until the automation system will seek the opened position stop at reduced speed
and will then closes fully. This serves to allow the system to acquire the travel parameters (length, closed and open position stops);
If the automation closes instead of opening, stop the run of the door (by cutting the photocells or closing the STOP contact),
invert the polarity of the motor and restart the procedure from the beginning.
2_ the door then opens automatically and closes again fully at normal speed, slowing as it approaches the travel limit stops/limit switches.
During these two stages, the system acquires, point by point, the force required to open and close the door;
3_ programming ends with the door in the closed position. To start regular operation, simply press the O/C button on the board, or the key
on the remote control (if programmed).
NOTE: if you want the control unit to perform a new parameter storing procedure, simply hold down the ENTER (O/C) key for 3 sec-
onds; the board will enter programming mode again and will run a new adjustment cycle, which will be stored in the memory, replac-
ing the previous one.
Note: by means of any adjustment device on the control panel (trimmers or dipswitches) perform a complete manoeuvre (opening
and closing) of the automation to apply the new settings.
After a power outage, the opener will perform a full cycle (opening + closing) at a slow speed to reset the ope-rating param-
eters to the values originally saved.
3.5 Logic settings
TRIMMER
T.C.A.
Automatic closing time setting trimmer. From 0 to 120 sec.
Turn clockwise to increase the length of time the door stays open.
FR
Trimmer for adjustment of force during the opening phase.
NOTE:
you can turn the FR TRIMMER to further increase or decrease obstacle sensitivity. Turning clockwise increases the motor's
operating force.
BJ
Trimmer that regulates the loosening of the belt/chain from the track at the end of the closing operation (available from version
5v12)
3.6 Dip-switches
1
on: at the end of opening, the door closes automatically after a time interval set on the trimmer A.C.T.;
off: closure requires a manual command;
2
on: with the automation running, a sequence of open/close commands activates a door sequence OPEN-CLOSE-OPEN-CLOSE, etc. (see also
dip switch 4);
off: in the same conditions, a sequence of open/close commands activates a door sequence OPEN-STOP-CLOSE-STOP-OPEN-STOP, etc.
(step-step function);
3
on: slowdowns both during opening and closing operations are reduced by 30% (they start after the factory settings' ones)
off: factory settings' slowdowns both during opening and closing operations
When changing the position of Dip-switch n°3, you must carry out the stroke setup procedure
through ENTER of PROG buttons.
4
on: NO-REVERSE function active; the door ignores the closing commands during opening and inverts the direction of door travel only in the
closing phase;
off: on activation of the open-close button, the direction of travel is inverted also in the opening phase;
5
on: the pre-flashing function is enabled;
off: the pre-flashing function is disabled;
6
on: the "photocell check" function is enabled;
off: the "photocell check" function is disabled. N.B. to be used when photocells are not used;
3.7_ Features of K691M
LED - DL3
As well as indicating the presence of power, this led indicates any errors by means of a set series of flashing signals:
•
Continuous flashing:
storage going on or unachieved setup
•
always lit:
normal operation;
•
1 flash:
backup battery voltage less than 11.3 Vdc;
Check the mains voltage, charge the battery, replace the battery;
•
2 flashes:
fototest error;
Disable fototest (dipswitch 6 set to OFF), check photocell operation and relative connection;
•
3 flashes:
mains power failure;
28