Refer to local regulations in the country of use for anything
that is not specifi cally covered in this manual. In
Italy, refer to standard UNI 10683 in addition to
any Regional or Local Health Authority regulations. If
the stove is to be installed in a block of apartments, consult
the block administration before installing.
VERIFY COMPATIBILITY WITH OTHER
DEVICES
The stove must NOT be installed in the same room as
extractors, type B heating appliances and other appliances
that may affect its operation. See regulation UNI 10683.
VERIFY THE POWER SUPPLY CONNECTION
(the plug must be accessible)
The stove is supplied with a power cable that is to be connected
to a 230V 50 Hz socket, preferably fi tted with a
magnetothermic switch. In the event that the power outlet is
not easily accessible, provide a device to cut off the power
supply (a switch) upstream of the stove (must be provided
by the customer). Voltage variations exceeding 10% can
damage the stove.
The electrical system must comply with the law; particularly
verify the effi ciency of the earthing system.
An inadequate earthing system can cause anomalies for which
Edilkamin cannot be held liable.
The power line must have a suitable cross-section for the sto-
ve's power.
FIRE PREVENTION SAFETY DISTANCES
The stove can be attached directly to brick and/or plasterboard
walls. In the case of combustible walls (wood, for
example), you must install adequate insulation in a non
combustible material. You are required to adequately insulate
the smoke exhaust pipe and the warm air channelling
pipe, as they reach high temperatures. All elements made
from combustible and/or heat-sensitive material located
adjacent to the stove must be arranged at a distance of no
less than 40 cm or otherwise be adequately insulated with
non combustible insulating material, and in any case materials
can not be placed at less than 80 cm in front of the
stove as they are directly exposed to the heat radiating
from the hearth.
AIR INTAKE
There must be an air inlet behind the stove with a minimum
diameter of 80 cm². This must be connected to the
outside in order to guarantee suffi cient air supply to the
stove for combustion.
The air intake must be connected to the dedicated nozzle on the
back of the stove (see pg. 23).
INSTALLATION
SMOKE OUTLET
The stove must have its own smoke outlet (the smoke
cannot be discharged into a smoke fl ue used by other
devices).
The smoke exhaust is expelled through the 8 cm-diameter
outlet located on the back, right side or top. The smoke outlet
must be connected to outside by means of suitable steel pipes
and must be free from obstructions. The stove smoke dischar-
ge must be connected with outside by means of steel or black
pipes EN 1856 certifi ed. The pipe line must be hermetically
sealed. The pipes must be sealed and insulated using materials
that are resistant to high temperatures(high temperature silicone
or mastic). The only horizontal section allowed may be up to
2 m long. It is possible to use up to two curves with a maxi-
mum angle of 90 ° (with respect to the vertical axis). A vertical
section of at least 1.5m and an anti-wind terminal is necessary
(if the discharge outlet is not in a chimney fl ue) (reference UNI
10683). The vertical duct can be internal or external. If the
smoke channel is outside, it must be appropriately insulated.
If the smoke channel is fi tted inside a chimney fl ue, the latter
must be suitable for solid fuel. If it is wider than 150 mm in
diameter it must be improved by entering a pipe that has a
suitable cross-section and is made of suitable material (e.g. 80
mm diameter steel). All sections of the smoke duct must be
accessible for inspection. The chimney pots and smoke ducts
connected to the solid fuel appliances must be cleaned once a
year (verify whether a specifi c legislation exists in your count-
ry). Failure to regularly inspect and clean the stove increases
the probability of a fi re occurring
in the chimney pot. In that case, proceed as follows: Do not
use water to extinguish the fi re; Empty the pellet hopper; Con-
tact specialist personnel before reigniting the stove.
TYPICAL EXAMPLES
Fig. 1
A:
insulated steel fl ue
B:
minimum height of 1.5 m and in any case above the height of the
roof gutter
C-E: air intake from inside room (minimum internal section: 80 cm²)
D:
steel fl ue, inside existing brick-built chimney.
CHIMNEY POT
The main characteristics are:
- an internal cross-section at the base, which is the same as that
of the chimney fl ue
- an outlet cross-section which is no smaller than twice that of
the chimney fl ue
- its position must be high enough to catch the wind and avoid
downdraft areas in turbulent wind, it must be high enough to
catch the wind and avoid downdraft areas in turbulent wind.
- 26
-
Fig. 2