STANDARDS
Mini conforms to the European directive
89/336/CEE on electrical safety.
SANICONDENS
®
INSTRUCTIONS INTENDED SOLELY FOR
QUALIFIED PROFESSIONALS
9
DISASSEMBLY
If a breakdown occurs, any service on the unit should be
carried out by a qualified engineer. In particular the
replacement of the power cable.
Disconnect the electrical supply before carrying out
work on the unit.
All manuals and user guides at all-guidesbox.com
1 0
TROUBLESHOOTING
INSTRUCTIONS RESERVED SOLELY FOR
QUALIFIED PROFESSIONALS
Disconnect the electrical supply before carrying out any work.
FAULT DETECTED
• The pump does not start
• The pump does not lift
1 1
GUARANTEE
parts and labour, subject to correct installation and use of
SANICONDENS
the unit.
PROBABLE CAUSES
• The pump is not
• Plug in the unit.
connected to the power
supply
• Check the mains voltage.
• Power cut
• Float blocked
• Clean the SANICONDENS
• Condensates inlet pipe
• Clean the SANICONDENS
blocked
• Non-return valve blocked
• Clean the valve.
• Discharge pipe blocked
• Clean the discharge pipe.
Mini SFA is guaranteed for 2 years for
®
ACTION NEEDED
®
Mini tank.
®
Mini inlet pipe.