Use
2.4
Limitations on use
● The Dräger Flame 3000 is not approved for use in oxygen-enriched
atmospheres.
● As the Dräger Flame 3000 responds to visible flames, it cannot be used in
locations where flare stacks and other open flames are within its field of view
without triggering false alarms.
● The Dräger Flame 3000 is unable to detect fires that are invisible to the
naked eye, such as those using pure hydrogen, methanol and sulphur as
fuel.
● The sensitivity of the Dräger Flame 3000 to flame is reduced by obscurants
such as smoke, fog and other airborne particulates. The Dräger Flame 3000
may be blinded by extremely dense obscurants.
● Although the Dräger Flame 3000 is insensitive to arc welding, arc welding
should not take place within 1 m of the flame detector.
2.5
Approvals
ATEX: Certificate number FM21ATEX0078, II 2 G Ex db IIC T4
IECEx: Certificate number IECEx FME 21.0005, Ex db IIC T4
FM: Class I, Div. 1, Groups B, C, D T4;
Class I, Zone 1, AEx/Ex db IIC T4,
ambient temperature: -60 °C to +85 °C
CE: GEC EN55022 & 082
For further information on approvals see declaration of conformity at the end of
this document or www.draeger.com/product-certificates.
8
2.6
Explanation of type-identifying marking and
symbols
The flame detector is fitted with a label that shows the certification and
conditions within which it can operate.
The following label is an example only.
FLAME 3000
TYPE:
SERIAL No:
YEAR:
Dräger SafetyAG & Co. KGa A
ENTRY:
Revalstraße 1
M25
½" NPT
Single
23560 Lübeck, Germany
AMBIENT: -60ºC +85ºC
M20
¾" NPT
Dual
WARNING: DO NOT OPEN WHEN EXPLOSIVEATMOSPHERE MAY BE PRESENT
3
Use
3.1
Prerequisites for installation
Observe the following:
● Ensure that the Dräger Flame 3000 has an unobstructed view of the areas
to be protected.
● Ensure that the mounting position is free from vibration or movement.
● Ensure that the mounting position has sufficient support for the Dräger
Flame 3000 and allows for horizontal adjustment.
● Ensure that the Dräger Flame 3000 is protected from sources of impact
damage and from being knocked out of alignment.
● Ensure that the area under observation has sufficient detector coverage for
all possible hazards (multiple detectors may be required) taking into account
any obstructions and congestion.
● Install the Dräger Flame 3000 as far away as possible from local sources of
possible electrical interference, such as X-rays, RF (radio frequency)
interference or electrostatic discharge.
● Minimize the exposure of the enclosure front cover window to contaminants
such as oil, water (deluge water, rain and sea spray), snow, and ice. Where
the Dräger Flame 3000 is to be mounted at a low level avoid contamination
from equipment situated above the mounting position.
● If dense smoke is expected to accumulate at the onset of the fire, the Dräger
Flame 3000 should be mounted 1 – 2 m below the ceiling level where
possible.
Instructions for use
TYPE 4, IP66
0158
II 2 G Ex db IIC T4
Gb
Class I DIV 1 GROUPS B,C,D,T4
3260
AMBIENT: -60ºC +85ºC
Class I Zone 1 AEx/Ex db IIC T4
Gb
AMBIENT: -60ºC +85ºC
AMBIENT: -60ºC +85ºC
FM21ATEX 0078
FM22US0029
IECEx FME 21.0005
FM22CA0023
Maximum Voltage: 30VDC
DO NOT REPAIR FLAME PATHS
Maximum Current: 250mA
SEAL CONDUIT WITHIN 18" OF ENCLOSURE ENTRANCE
WARNING: REFER TO FLAME 3000TECHNICAL MANUAL BEFORE INSTALLING OR MAINTAINING THIS UNIT
|