Operating Instructions
6.1.2
Start X.TUNE
But-
Operation:
Description
ton
1
5s
Start X.TUNE by pressing the 1 button for
5 s*
*Starting X.TUNE also possible with communication software.
NOTE!
If LED 1 lights up red after the X.TUNE:
► Execute X.TUNE again.
► Possibly perform a device restart.
► After setting the DIP switches, screw the transparent cover of the type SPC positioner back on.
NOTE!
Breakage of the pneumatic connecting pieces due to rotational effect.
► When unscrewing and screwing in the transparent cover, do not hold against the actuator of the valve, but against the basic
housing.
CAUTION!
Damage or functional failure due to ingress of dirt and moisture.
► To comply with protection rating IP65/IP67, screw the transparent cover in as far as it will go.
LED 2 flashes at 5 Hz. The device is in the NAMUR state
Function check, LED 1 lights up orange.
If X.TUNE is successfully completed, the NAMUR state is reset.
The changes are automatically stored in the memory (EE-
PROM).