Operating Instructions
+
1
2
I
3
+
4
U
Supply voltage
Pin
Assignment
3
Supply voltage GND
4
Supply voltage +
Output signals to the control station (only with analog output variants)
Pin
Assignment
8
Analog position feedback +
7
Analog position feedback GND
4.5.2
Electrical connection procedure
1.
Connect the type RPC positioner according to the tables. After applying the operating voltage, the RPC positioner type is in ope-
ration.
2.
Now make the required basic settings and adjustments for the positioner. The procedure is described in chapter " Putting into
operation type RPC".
4...20 mA
GND
+24 V DC
External circuitry, signal level
3
4
External circuitry, signal level
8
7
+
1
4...20 mA
I
3
+24 V DC
+
4
U
24 V DC ± 25% - max. residual ripple 10%
+ (4 - 20 mA)
GND
Type RPC positioner
GND