Operating Instructions
Operating mode AUTOMATIC (Slide DIP switch 4 OFF)
5.3
Display of the LEDs
1
2
5.4
Device status display
LED 1 (RGB) indicates the device status.
The user can set the following LED mode to indicate device status and valve position:
NAMUR mode
•
Valve mode
•
Valve mode and warnings (factory setting)
•
Permanent color
•
LED off
•
Button
Function
1
Pressing and holding for 5 s starts the X.TUNE function
2
-
1 and 2
Longer than 10 s (< 30 s, LED 2 flashes at 5 Hz): Device restart
Longer than 30 s (LED 2 flashes at 10 Hz): Reset the device to factory settings
No. Designation
1
LED 1 (RGB): Display of device status and valve position
2
LED 2 (green): Display of the bus status
Feedback when pressing the buttons to
start the functions
X.TUNE
•
Device restart
•
Reset to factory settings
•
Type RPC positioner
27