Operating Instructions
5.2.1
Slide switch functions
ON DIP
1 2 3 4
* Can be changed with communication software.
But-
Function
ton
1
ON
Reversal of the operating direction of the setpoint value (20 - 4 mA corresponds to
0 - 100%), falling (DIR.CMD)
OFF
Normal operating direction of the setpoint value (4 - 20 mA corresponds to 0 -
100%), increasing
2
ON
Tight-closing function active. The valve closes below 2%* and opens completely
above 98%* of the setpoint value (CUTOFF)
OFF
No tight-closing function
3
ON
Correction characteristic for adjusting the operating characteristic (CHARACT)*
OFF
Linear characteristic
4
ON
Operating state Manual
OFF
Operating mode AUTOMATIC (AUTO)
Type RPC positioner
25