Functioning Limits - Hitecsa EQPL-B 4360 Manual Del Operador

Enfriadoras de agua y bombas de calor reversibles monobloque con condensación por aire y refrigerante ecológico r410a. serie con compresores herméticos scroll
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

I.5

FUNCTIONING LIMITS

Summer mode
50
45
40
15
0
-8
-4
-5
-10
-15
50
48
42
15
0
-8
-4
-5
-10
-15
T (°C)
Outdoor air temperature (B.S.)
t (°C)
Water temperature
Standard functioning
Summer operation with condensing control FI10 (as per standard in S version)
Summer operation with condensing control FI15 (as per standard in SS version)
Functioning with partialised cooling capacity
Winter mode with FI10 or FI15 condensation control (FI10 standard in version S and FI15 standard in version SS)
In summer mode:
Maximum water inlet temperature 23°C.
Minimun water pressure 0,5 Barg.
Maximum water pressure: 10 Barg / 6 Barg with ASP
Maximum water pressure 10 Barg (with P/DP accessory).
Maximum water pressure 6 Barg (with ASP/ASDP accessory).
Permitted temperature differentials through the heat exchangers
○ Temperature differential at the evaporator AT = 3 ÷ 8°C with all compressors on) for machines with a "Standard" set-up. The maximum and minimum
temperature differential for the Pump and Tank&Pump machines is related to the performance of the pumps that must always be verified via HITECSA
software.
For t(°C), < 5°C (accessorio BT) it is COMPULSORY to specify the unit's operating temperature when placing the order (evaporator glycol water
inlet/outlet) in order to allow for its correct parametrisation. Condensing control FI10 or FI15, where not already carried out as standard, is also
compulsory. Use of antifreeze solutions: see "Use of anti-freeze solutions"
Models
Versions
(1)
Water temperature (IN/OUT) 12/7 °C.
(2)
Maximum outdoor air temperature with unit in standard operation running on full.
(3)
Maximum outdoor air temperature with unit in silenced mode.
(4)
Maximum outdoor air temperature with unit in partialised cooling capacity.
B-S-SS
5
15 18
10
T
5
15
18
10
4360÷8860
B
Tmax = 45°C (1) (2)
Tmax = 50°C (1) (4)
In winter mode:
Minimum water inlet temperature 18°C.
Maximum water inlet temperature 51°C
4360÷8860
4385÷8920
S
Tmax = 42°C (1) (3)
Tmax = 48°C (1) (2)
Tmax = 45°C (1) (2)
Tmax = 50°C (1) (4)
Tmax = 50°C (1) (4)
50
Winter mode
54
50
45
B-S-SS
40
35
30
24
-7 -5
0
5
10
15
20
55
50
45
T
40
35
30
24
-10
-5
0
5
10
15
20
4385÷8920
T
Q
Tmax = 40°C (1) (3)
Tmax = 45°C (1) (2)
Tmax = 50°C (1) (4)