Final warnings on connections
After connecting to the cable connectors, tie the
network voltage cables and the cables for external
components (accessories, peripherals), respectively,
close to the terminal strip, thus ensuring the
network voltage cables and the low voltage cables
are separated.
This prevents the network's live parts from coming
into contact with the safety low voltage parts in the
event of accidental cable disconnection.
7
STARTING UP
Settings for the facility to fulfil safety
requirements
The torque regulator of the control panel must
be set to respect the values indicated in
Standard EN 12453:2000. All measurements
must be made in line with the method
described in Standard EN 12445:2000.
UNPACKING AND INSTALLATION
When connecting rigid or flexible pipes and cable
sleeves, use bushing conforming to IP55, such as the
plastic box containing the board.
Using an emergency button installed close to
the automation device (connected to the
control
panel's
recommended, so the door can be stopped
immediately in the event of danger.
User instruction
1 Instruct the user with regards to the use and
maintenance of the installation and provide him/her
with the user guide.
2 Signpost
the
door,
automatically and indicating how to operate it
manually.
Where
appropriate,
operation is using the remote control.
STOP
terminal)
is
showing
that
it
opens
indicate
that
IZAR chain transmission operator
39