Installation
n
DIP switch setting
Name
Function
SW1-KNX PCB Reset KNX PCB
SW1-H-LINK
Not avaliable
PCB
SW2
Reset
SW3
Not available
(TELE)
SW4
Configuration
SW5
Configuration
SW6
Configuration
SW7
Options 2
SW8
Options 1
(Application type)
SW9
Not available
SW10
HC-A16KNX
address
SW11
H-LINK DSW
D4, D11
H-LINK
D5
Not used
D6
Units configuration
alarm
D7
Power
D9/D10
Not used
D12
KNX
D13
Operation
Factory setting
Reset button. To be used in case of KNX communication has been locked.
All in off (no function)
Reset button. To be used in case of program has been locked
Factory purposes. Never change it
Setting functions
Setting functions
Setting functions
Configuration as MASTER HC-A16KNX: SW7-1=ON.
Only one HC-A16KNX can be set as a MASTER HC-A16KNX. Setting by default.
Configuration as SLAVE HC-A16KNX: SW7-1= OFF.
It should be 1 HC-A16KNX configured as MASTER, all the rest of HC-
A16KNX must be configured as SLAVE
All in off (no function)
All in off (no function)
HC-A16KNX address from 0 to 31 by pins 1 to 5
SW11-1: H-LINK end resistance
SW11-2: Not used
H-LINK transmission
ON- No alarms
OFF- Units not configured
Power supply ON/OFF
-
Internal communication between the KNX PCB and the H-LINK PCB.
Normal software operation
Description
PMML0193A rev.2 - 06/2010
11