Installation
Step
Action
number
1
Press SW4 for 3 seconds
2
Press SW4
3
Press SW4
4
Press SW4
5
Press SW4
6
Press SW4
For "id" 01 repeat steps 1 to 6
7
Press SW4 for 3 seconds
8
Press SW4
9
Press SW4
10
Press SW4
11
Press SW4
12
Press SW4
... Repeat steps 1 to 6 for all the rest "Id"
91
Press SW4 for 3 seconds
92
Press SW4
93
Press SW4
94
Press SW4
95
Press SW4
96
Press SW4
97
Press SW4 for 3 seconds
7 segments (display)
id
OO
oU
--00
iU
--00
id
OO01
oU
--00
iU
--01
id
OO31
oU
--01
iU
--15
Nothing displayed
Remarks
Configuration mode selected
Id selection (IU No.) from 0 to 15 by pushing
SW5 ▲ or SW6 ▼
Refrigerant cycle address
Refrigerant cycle address selection from 0 to 15 (e.g. 00)
(by pushing SW5 ▲ & SW6 ▼)
Indoor unit address
Indoor unit address selection from 0 to 15 (e.g. 00)
(by pushing SW5 ▲ & SW6 ▼)
Configuration mode selected
Id selection (IU No.) from 0 to 15 by pushing
SW5 ▲ or SW6 ▼
Refrigerant cycle address
Refrigerant cycle address selection from 0 to 15 (e.g. 00)
(by pushing SW5 ▲ & SW6 ▼)
Indoor unit address
Indoor unit address selection from 0 to 15 (e.g. 01; push
SW5 once)
(by pushing SW5 ▲ & SW6 ▼)
Configuration mode selected
Id selection (IU No.) from 0 to 15 by pushing
SW5 ▲ or SW6 ▼
Refrigerant cycle address
Refrigerant cycle address selection from 0 to 15 (e.g. 01;
push SW5 once))
(by pushing SW5 ▲ & SW6 ▼)
Indoor unit address
Indoor unit address selection from 0 to 15 (e.g. 15; push
SW6 once)
(by pushing SW5 ▲ & SW6 ▼)
Exit from configuration mode