Descargar Imprimir esta página

Federal Signal Global G-STR Instrucciones De Instalación Y Mantenimiento página 24

Ocultar thumbs Ver también para Global G-STR:

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation and Maintenance Instructions
Table 3 Choosing cable-entry devices for Equipment
Models
G-STR-XXX-D-X
(Ex db surface
mount)
G-STR-XXX-T-X
(Ex db trunnion
mount)
G-STR-XXX-E-X
(Ex db surface
mount)
G-STR-XXX-D-X
(Ex db surface
mount)
G-STR-XXX-T-X
(Ex db trunnion
mount)
G-STR-XXX-E-X
(Ex db e surface
mount)
24
All manuals and user guides at all-guides.com
in Potentially Explosive Atmospheres
Ex Atmospheres
Gas
Gas
Dust
Model G-STR Global Series Strobe Beacon
Cable Entry Devices (cable
glands, stopping plugs, etc.)
Cable entry devices shall
be equipment certified as
flameproof. To maintain the
ingress protection of the
flameproof beacon enclosure,
we recommend the cable entry
device be IP66 certified.
For the flameproof beacon
enclosure, cable entry devices
shall be equipment certified
as flameproof. To maintain
the ingress protection of the
flameproof beacon enclosure
we recommend the cable
entry device be IP66 certified.
For the increased safety
terminal enclosures (terminal
boxes), cable entry devices
shall be equipment certified
as increased safety and shall
maintain an IP rating of IP54.
Cable entry devices for
the Beacon and terminal
enclosures shall be equipment
certified as dust protected. To
maintain the ingress protection
of the beacon and terminal
enclosures the cable entry
devices shall be IP6X certified.

Publicidad