Descargar Imprimir esta página

Franklin Electric Smartstart SSP3 Serie Manual Del Propietário página 4

Arrancador de bomba ssp1

Publicidad

Idiomas disponibles

Idiomas disponibles

INSTALLATION
Electrical Installation
I/O Wiring Connections
NOTE: Use 26~14 AWG
wire and torque to 3.5 lb-
in for control wiring (D3/
D4/D5, C-/C+, and T-/TI/
T+). Use 20~12 AWG wire
for control wiring (D1/D2
and O1/O2).
1. D3/D4/D5 Pilot Device
Input: Connections for a
factory installed 3-position
(HOA) switch for motor
control
2. D1/D2 Dry Auto Input:
Close this input to send a
run command to the soft
starter when in Auto mode.
(N.O. dry contact or tran-
sistorized input)
3. O1/O2 Fault Relay Output:
Normally open relay con-
tacts that close in the event
of a fault condition. Rated
for 120 VAC, 0.6 A
4. C-/C+ Contactor Output: Provides a 24 V output to close the contactor when the motor starter is
commanded in either Hand or Auto mode. Once the contactor is closed, the output drops to 2-4 V
to maintain contactor closure while optimizing efficiency. Only for use with Franklin Electric contac-
tor with 24 VAC coil (0.875 A Max).
4
Amps
Overload Setting
(Range varies per model)
Keypad
PCB Power
H1 and H4 terminals apply
to combination units only
H1
H4
30
0
UNDERLOAD
Hand
Pilot
1
Auto
Devices
Common
Dry
Auto
2
Input
Run
Relay
3
Fault
Outputs
Contactor
4
Coil
50
70
100
%
OFF
AUTO
HAND
X
X
Normally
Open Input
Alarm Lamp
12-250VAC
A2
CON
A1

Publicidad

loading