Descargar Imprimir esta página

Eaton Tripp-Lite Serie Guía De Usuario página 21

Publicidad

Idiomas disponibles

Idiomas disponibles

C C h h a a p p t t e e r r 5 5 T T r r o o u u b b l l e e s s h h o o o o t t i i n n g g
5 5 . . 1 1
A A u u d d i i b b l l e e A A l l a a r r m m s s a a n n d d C C o o n n d d i i t t i i o o n n s s
The Tripp Lite Series UPS system has an audible alarm feature to alert you of potential power problems. When
the alarm is activated, the alarm sounds at different intervals according to a particular condition. Use
determine and resolve the UPS alarms and conditions.
Table 3. Troubleshooting
Problem
No LEDs are displayed on
the front panel
The UPS is always on
battery mode
The UPS alarm sounds
continuously
(If the alarm is not
disabled in Line Mode
3.5 Audible Alarm Enable/
Disable
Backup time too short
Possible Cause
The UPS is not turned on
Battery Voltage is to too low
Battery fault
The power cord is disconnected
Overload in Line mode
Overload in Battery mode
(see
)
Output short fault
Battery voltage is too low
Battery is defective
Verify that the UPS is connected to a valid power source and
press the power button again.
Charge the battery for at least six hours.
Verify that the UPS is connected to a valid power source.
Remove any unnecessary load and verify that the load does not
exceed the defined UPS specifications. If the problem persists,
contact Eaton support.
Remove any unnecessary load and verify that the load does not
exceed the defined UPS specifications. If the problem persists,
contact Eaton support.
Disconnect the load. Check the equipment for potential issues.
Plug the devices back in, one at a time. If the problem persists
contact the Eaton support.
Charge the battery at least six hours.
Tripp Lite Series UPS Systems User Guide 93470A—Rev A
Table 3
Solutions
Replace the battery.
Replace the battery.
to
15

Publicidad

loading