Hotswap Mbp Module Operation; Ups Start-Up With The Hotswap Mbp Module; Hotswap Mbp Module Test; Ups Connection Without A Flexpdu Or Hotswap Mbp Module - Eaton Powerware 5130 Serie Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 97
2. Installation

HotSwap MBP module operation

UPS start-up with the HotSwap MBP module

1 - Check that the UPS is correctly connected to the HotSwap MBP module.
2 - Set switch (53) to Normal position.
3 - Start the UPS by pressing the ON/OFF button (24) on the UPS control panel.
The load is supplied by the UPS.
LED (51) "UPS ON - OK to switch" on the HotSwap MBP module goes ON.

HotSwap MBP module test

1 - Set switch (53) to Bypass position and check that the load is still supplied.
2 - Set switch (53) back to Normal position.

2.7 UPS connection without a FlexPDU or HotSwap MBP module

Check that the indications on the name plate located on the back of the UPS correspond to the AC-power source and
the true electrical consumption of the total load.
Note. The UPS charges the battery as soon as it is connected to the AC-power source, even if button (24) is not pressed.
Once the UPS is connected to the AC-power source, eight hours of charging are required before the battery can
supply the rated backup time.
- Page 12
MAU-00069 AA
51
52
53
7
9
10
8
35
32
31
The HotSwap MBP module has a rotary
switch (53) with two positions:
Normal - the load is supplied by the UPS,
Bypass - the load is supplied directly by the
AC-power source.
1 - PW5130 1250 / 1750 : connect the UPS
input socket (10) to the AC-power source
using the cable of the protected equipment.
PW5130 2500 / 3000: connect the supplied
cable (31) (250 V - 16 A) to the socket (10),
then to the AC-power source.
2 - Connect the loads to the UPS using the
cables (32).
It is preferable to connect the priority loads to
the four outlets marked (9) and the non-
priority loads to the four outlets marked (8)
that can be programmed in pairs (1 and 2).
For the PW5130 2500 / 3000 models,
connect any high-power devices to the 16 A
outlet (7).
To program shutdown of outlets (8) during
operation on battery power and thus optimise
the available backup time, the UPS
Configuration Tool communication software
is required.
3 - Fit the connection securing system (35)
that prevents the plugs from being pulled out
accidentally.

Publicidad

Tabla de contenido
loading

Tabla de contenido