4. Personalisation using external software

Download the
instructions.
You can modify the following setting parameters (a detailed explanation is available in the UPS Configuration Tool
software).
Main-output personalisation
Function
Output voltage on battery power
Overload alarm threshold
Voltage-threshold personalisation
Function
High threshold for transfer to battery
Low threshold for transfer to battery
Fader activation threshold
Booster activation threshold
Maximum input-voltage range
(1) Low threshold for transfer to battery is 150 V.
UPS-sensitivity personalisation
Function
UPS-sensitivity level
UPS ON/OFF personalisation
Function
Automatic start
Cold start
Forced shutdown
Energy-savings mode
UPS ON/OFF controlled by software
Battery level before restart
Battery personalisation
Function
Battery-test intervals
Low-battery warning
Battery protection against deep discharge
Audio alarm
Additional battery module (PW5130 models only)
- Page 16
MAU-00069 AA
"
"
UPS configuration Tool
from the website www.powerware.com and install it following the on-screen
Factory setting
230 Volts AC
105%
Factory setting
294 Volts AC
160 Volts AC
265 Volts AC
184 Volts AC
Disabled
Factory setting
Normal
Factory setting
Enabled
Enabled
Enabled
Disabled
Enabled
0%
Factory setting
Weekly
20%
Enabled
Enabled
Automatic detection of number
of battery modules
Other available settings
200/208/220/240 Volts AC
30/50/70%
Other available settings
271 to 294 Volts AC
160 to 180 Volts AC
244 to 265 Volts AC
184 to 207 Volts AC
(1)
Enabled
Other available settings
High or low
Other available settings
Disabled
Disabled
Disabled
Enabled
Disabled
0 to 100%
Other available settings
No test / daily test / monthly test
0 to 100%
Disabled
Disabled
For specific batteries, from 25
to 81 Ah