Position of the teach spot for the magnet
The level probe has a teach wire / teach pin and a teach spot this is located on the cover of the probe.
Probe with stainless steel connection head
Teach spot
LED display
Behaviour in operation, depending on the setting.
Table 3
Factory reset
Measurement
Adjustment active
Setting warning
Temperature warning
Permissible electronic temperature
exceeded/undershot
Fault / malfunction
Sensor break, missing BE connection,
electronic fault
The orange LED is only there for error information.
Adjustment
The probes are supplied with a factory calibration for a reference arrangement. After installation in the
application, a one-time empty calibration to the empty container is mandatory during commissioning.
Only then will the level measurement with DK compensation become active.
Optional:
A one-time full adjustment with any medium overwrites the factory calibration and optimally adjusts the
probe to the application.
Probe with rope housing
Teach spot
LED green /
orange
LED green /
yellow
Single pulses, permanent
(green)
Permanently on (green)
Fast pulsing (green)
Double pulse, single
(orange)
Double pulse, permanent
(orange)
Permanently on
(orange)