Electrical Wiring
(B) Definition and description of SW03
Address
SW03_1
setting mode
Code-set
indoor unit
SW03_2
address and
~
centralized
SW03_8
controller
address
(Note 2)
Note 2:
• Set the address by code when connecting the centralized controller or gateway or charge system.
• Address of centralized controller = communication address + 0 or +64.
SW03_ 2=OFF, address of centralized controller =communication address+0=communication
address
SW03_2=ON, address of centralized controller=communication address+64 (applies when
centralized controller is used, and there are more than 64 indoor units)
• To use with 0010451181A, it is required to use code for address setting. Set SW03_1 =0N and SW03_
2=OFF; SW03_3, SW03_ 4, SW03_5, SW03_6, SW03_7 and SW03_8 are address codes which are
set according to actual addresses.
Code setting of wired controller
Taking the 40VCW217FQEE wired controller as an example, the code setting is as follows.
Please refer to the controller manual for details
DIP switch
On/off state
On
Sw1-1
Off
On
Sw1-2
Off
On
Sw1-3
Off
On
Sw1-4
Off
0
1
[2]
[3]
[4]
[5]
[6]
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
...
...
...
...
...
0
1
1
1
1
1
0
0
0
0
1
0
0
0
0
1
0
0
0
0
...
...
...
...
...
1
1
1
1
1
Function
Slave wired controller
Master wired controller
Ambient temperature display on
Ambient temperature display off
Collect the ambient temperature of the PCB
Collect the ambient temperature
of the wired controller
Old protocol (Protocol 1)
New protocol self-adaptation
(Protocol 2 and Protocol 3)
21
Automatic setting (default)
Code-set address
Address of indoor
[7]
[8]
unit
0#
0
0
(Default)
0
1
1#
1
0
2#
...
...
...
1
1
63#
0
0
0#
0
1
1#
1
0
2#
...
...
...
1
1
63#
Address of
centralized
controller
0#
(Default)
1#
2#
......
63#
64#
65#
66#
...
127#
Default setting
Off
Off
Off
Off