Descargar Imprimir esta página

Daikin RXYQ72XAYC Serie Manual De Operación página 7

Sistema de aire acondicionado vrv

Publicidad

Idiomas disponibles

Idiomas disponibles

What to do before Operation
This operation manual is for the following system with standard control. Before initiating operation, contact your local dealer for
the operation that corresponds to your system type.
If your installation has a customized control system, ask your local dealer for the operation that corresponds to your system.
RXYQ series
6
7
Operation Range
Outdoor temperature
Indoor temperature
Indoor humidity
Note
• Cooling operation:
If the air conditioner is operated continuously while the indoor temperature is 70°FDB (21°CDB) or below and the humidity is 80% or
over, the interiors of the indoor units may cause icing and water leakage may result.
• Heating operation:
The air conditioner may stop operating for the protection of the machine if the outdoor temperature is 70°FDB (21°CDB) or over.
English
1. Outdoor unit
2. Indoor unit
3. Remote controller
4. Inlet air
5. Outlet air
6. Cool/Heat selector
7. Refrigerant piping
COOLING
23 to 110°FDB
–13 to 60°FWB
(–5 to 43°CDB)
(–25 to 16°CWB)
57 to 77°FWB
59 to 80°FDB
(14 to 25°CWB)
(15 to 27°CDB)
80%
HEATING
3

Publicidad

loading