ARES UPS User Manual
Charge Current (Max.) Standard
Supplementary Charger (Max.)
Recharge time (to 90%)
Floating Mode Charging Voltage
Bulk Mode Charging Voltage
Transfer time
AC to DC
Inverter to Bypass
Programmable outlet
Programmable relay
Protection
Short Circuit
Battery
EPO
Over Temperature
Physical
2U
model
Dimensions
W x H x D
Tower
model
2U
model
Net Weight
Tower
model
Interface
Compatible Platforms
Environmental
Operating Temperature
Noise Level
Relative Humidity
Standards and Certifications
Safety
EMC
Markings
22
Charger
2.1A
5A x 1
4hr
40.9V±1%
42.3V±1%
Normal Mode : Output Breaker/Electronic Circuit
Battery Mode : Output Breaker/Electronic Circuit
Battery Mode: UPS shuts down immediately
(mm)
440x88x405
(inches)
17.3x3.5x15.9
(mm)
154x214x388
(inches)
6.0x8.8x15.3
(kg)
11.7 kg
(lbs)
25.8 lbs
(kg)
11.6 kg / 25.6 lbs
(lbs)
1.5A
4A x 2
4hr
81.9V±1%
84.6V±1%
0 ms
4ms(Typical)
support 2 output groups
Bypass mode : Breaker
ABDM
UPS shuts down immediately.
Normal Mode: Transfer to Bypass Mode
440x88x600
17.3x3.5x23.6
192x250x475
7.5x9.8x18.6
21.8 kg
48 lbs
22.2 kg / 48.9 lbs
Microsoft Windows series, Linux, Mac, etc.
Operating : 0ºC ~ 40ºC (32ºF to 104ºF)
≦ 50dB
Storage : -10ºC ~ 50ºC (14ºF to 122ºF)
0-90% (without condensation)
IEC/EN 62040-1
EN62040-2, EN61000-3-2, EN61000-3-3
CE, UKCA
1.5A
4A x 2
6hr
81.9V±1%
84.6V±1%
440x88x600
17.3x3.5x23.6
192x320x451
7.5x12.6x17.7
24.6 kg
54.2 lbs
29.8 kg / 65.7 lbs

Publicidad

loading

Este manual también es adecuado para:

Ares 230v-2kAres 230v-3k