DALI Gateway DALI64 KNX-S, DALI Gateway DALI128 KNX-S
Attach the cover cap to the bus cable connection as protection against hazard-
ous voltages.
If the display (8) shows Er (error), an installation fault occurred that causes mains
voltage to reach the DALI cable. In this case disconnect the device and the DALI
devices from mains voltage and disconnect bus voltage. Correct installation.
4.2
Commissioning
The device can be put into operation, after mounting of the device and connection of
the bus line, the mains supply and the DALI cables. The following procedure is gen-
erally recommended...
Commissioning the device
Switch on the mains supply of the gateway.
Switch on the bus voltage.
Voltage check: When the programming button is pressed, the red program-
ming LED must light up.
Configure and program the physical address with the help of the ETS
Download the application program using the ETS.
Commission the DALI system using commissioning software (DCA).
Download the application program using the ETS again.
The gateway is ready for operation.
It is not explicitly necessary to carry out DALI commissioning and reprogram
the application program if the gateway has been integrated into an existing
DALI installation (e.g. when replacing a device of the same type) and contin-
82406608
Figure 3: DALI gateway connection example, 2fold