ues to be used with an unchanged DALI configuration (same short addresses,
device types, group assignments, etc.). This is the case, for example, if a
device is copied unchanged in the ETS project design or a configuration tem-
plate is imported.
No ETS programming is possible if no mains voltage supply is connected.
Safe-state mode
If the device does not work properly - for instance as a result of errors in the project
design or during commissioning - the execution of the loaded application program
can be halted by activating the safe-state mode. In safe-state mode it is not possible
to control the DALI operating devices via the KNX or by manual operation. The gate-
way remains passive in safe-state mode, since the application program is not being
executed. Only the system software is still functional so that the ETS diagnosis func-
tions and also programming of the device continue to be possible.
Activating safe-state mode
There are two options for activating the safe state mode.
Option 1:
Switch off the mains voltage supply.
Wait approx. 10 seconds.
Press and hold down the programming button.
Switch on the mains supply. Release the programming button only after the
programming LED starts flashing slowly.
The safe-state mode is activated.
Option 2:
Prerequisite: The mains voltage supply must be switched on without interruption.
Switch off the bus voltage or disconnect the bus terminal.
Press and hold down the programming button.
Switch on the bus voltage or attach the bus terminal. Release the program-
ming button only after the programming LED starts flashing slowly.
The safe-state mode is activated.
Even in safe-state mode, a brief press of the programming button can switch
the programming mode on or off as usual as long as the bus power supply is
switched on. The programming LED then stops flashing, even though safe-
state mode is still active.
Deactivating safe-state mode
Switch off the mains voltage supply (wait approx. 10 s),
or
82406608