9
Electrical connections
16
PE
MAINS
L
220-240V
N
~50-60 Hz
2
3
4
VCC
A
5
B
GND
A
6
B
GND
• The power cord must be PVC sheathed cord (model 60227 IEC 53 (RVV))
2008/IEC 60227-5:2003, with CCC certificate for chinese market).
• The three power cable conductors must have a nominal cross-section of no less than 0.75 mm
connected to the earthing terminal of the device.
• To connect the HMI remote display to the machine, use cables with a
section between 0.35 mm
the display connection cable should be kept separate or away from the
power cables, if there are problems of electromagnetic interference
from other devices installed in the environment (which produce
malfunction of the display), it is recommended to use shielded cables.
• To connect the pre-heater and post-heater, use cables with a minimum
section of 0.5 mm
.
2
1
220-240V
~50-60 Hz
220-240V
~50-60 Hz
and 2.5 mm
. Max length 80 m. Given that
2
2
GNYE
BN
L
BU
N
BN
PREH
BU
N
BN
POSTH
BU
N
BK
BOOST
BK
GND
BK
VCC
BK
A
BK
B
BK
GND
BK
A
BK
B
BK
GND
1
Mains 2 poles switch
2
Preheater (remote 220-240Vac relay coil )
3
Postheater (remote 220-240Vac relay coil )
4
Dry contact (remote switch / relay )
5
Remote HMI Slave
6
Remote Modbus Master Unit - RS485
, meet the requirements of GB/T 5023.5-
and a yellow-green core
2
17
MAINS
PREH POSTH
ENGLISH
MAINS
PREH
POSTH
BOOST
HMI
MODBUS
35