11. Connect the other HMI remote control
12. Reconnect the HRU to the electrical grid
13. Wait about 30 sec – 1 minute: the LED symbol
14. At the end of the process the HRU will go back to normal functioning.
15. Enter into the USE MENU with password 23 from the local HMI display on the machine
16. Change parameter "MBUD ID" so that it is different from 1 and different from that of the remote display: for example,
enter the number 2 and press
17. End
10.6 Holiday
Special mode of operation: manually enabled and useful if the user leaves the room
for a longer period of time. Operation includes:
- fixed "30% less than the Minimum " speed (no other speeds, no OFF equipment);
- environment sensors not enabled (remote inputs not actived);
- bypass always closed.
NOTE: Activating the Mode "Holiday" will be deactivate other product functionings/selections.
To re-activate other product functionings/selections, need to deactivate the Mode "Holiday" before. For more
details on how to activate / deactivate the function, see "Activating / deactivating Holiday" in the paragraph
"Control panel functions"
10.7 Post-ventilation
This kind of function is automatically activate after:
1. every time Pre-Heater is turned off (if Pre-Heater installed): both motor-fans active (about 3 minutes) to avoid overheating
2. every time you turn the Appliance off : indoor air is extracted at the max speed (about 2 minutes) to avoid condensate
presence on the heat exchanger.
This is a normal system procedure and should not be perceived as a malfunction.
10.8 Program
Special mode of operation: manually enabled and allows the user to program weekly air speeds. In fact, it allows you to
assign up to 6 time bands with different speeds, including stopping the equipment. When the function is active, the message
"Progr." Appears on the display: see "Home Page" in the "Control panel functions" section. However, the speeds can be
manually changed even at specified intervals:
in this case the word "Prg" will flash for 30 minutes and after it will go back to the setted speed
of the weekly time band, If in this 30 min any other function will change the speed, this 30 min timer
will go back to 0. For more details on setting the time slots and dates, see "PRG Crono" in the "Control panel functions"
section. For details on how to activate / deactivate the function, see "Activating / deactivating Program" in the "Control panel
functions" section.