Applicable controls
REQUIREMENT
When the air conditioner is used for the first time, it will
take some moments after the power has been turned on
before the remote controller becomes available for
operations: This is normal and is not indicative of
trouble.
• Concerning the automatic addresses (The automatic
addresses are set up by performing operations on the
outdoor interface circuit board.)
While the automatic addresses are being set up, no
remote controller operations can be performed. Setup
takes up to 10 minutes (usually about 5 minutes).
• When the power is turned on after automatically
address setup, it takes up to 10 minutes (usually
about 3 minute) for the outdoor unit to start operating
after the power has been turned on.
Before the air conditioner was shipped from the factory,
all units are set to [STANDARD] (factory default). If
necessary, change the indoor unit settings.
The settings are changed by operating the wired remote
controller.
* The settings cannot be changed using only a wireless
remote controller and simple remote controller by itself
so install a wired remote controller separately as well.
 Applicable controls setup
(settings at the site)
Remote controller model name:
RBC-ASCU11*
Basic procedure
Be sure to stop the air conditioner before making
settings.
(Change the setup while the air conditioner is not
working.)
CAUTION
CAUTION
Set only the Code No. shown in the following table: Do
NOT set any other Code No.
If a Code No. not listed is set, it may not be possible to
operate the air conditioner or other trouble with the
product may result.
27-EN
3,6
2,4,5
4,5
1
7
1
Push and hold menu button and [
] setting
button simultaneously for 10 seconds or more.
• After a while, the display flashes as shown in the
figure. "ALL" is displayed as indoor unit numbers
during initial communication immediately after the
power has been turned on.
Indoor unit No.
2
Each time [
] [
] setting button is pushed,
indoor unit numbers in the group control
change cyclically. Select the indoor unit to
change settings for.
• The fan of the selected indoor unit runs. The
indoor unit can be confirmed for which to change
settings.
3
Push OFF timer button to confirm the
selected indoor unit.
Code No.
Set data
– 122 –
4
Push the menu button to make Code No. [
]
flash. Change Code No. [
] with [
] [
]
setting button.
5
Push the menu button to make Set data
[
] flash. Change Set data [
] with
[
] [
] setting button.
6
Push OFF timer button to complete the set up.
• To change other settings of the selected indoor
4
unit, repeat from Procedure
.
7
When all the settings have been completed,
push ON/OFF button to finish the settings.
(Return to the normal mode).
"
" flashes and then the display content
disappears and the air conditioner enters the
normal stop mode. (The remote controller is
unavailable while "
" is flashing.)
• To change settings of another indoor unit, repeat
1
from Procedure
.
 Filter sign setting
According to the installation condition, the filter sign term
(Notification of filter cleaning) can be changed. Follow to
the basic operation procedure
1
2
3
4
5
6
7
(
).
[01]
4
• Specify
for the Code No. in Procedure
.
5
• For the set data in Procedure
, select the set data of
filter sign term from the following table.
Set data
Filter sign term
0000
None
0001
150 H
2500 H
0002
(Factory default)
0003
5000 H
0004
10000 H
• The filter sign may be unavailable depending on the
remote controllers.
 External static pressure
settings
To set the external static pressure, refer to the "Fan
characteristics" in 6 Duct design.
Set up a tap change based upon the external static
pressure of the duct to be connected.
To set up a tap change, follow to the basic operation
procedure
1
2
3
4
5
6
7
(
).
[5d]
4
• Specify
for the Code No. in procedure
.
5
• For the set data of procedure
, select a set data of
the external static pressure to be set up from the
following table.
Set data
External static pressure
0000
10Pa
Standard (Factory default)
0001
20Pa
High static pressure 1
0003
30Pa
High static pressure 2
0004
40Pa
High static pressure 3
0006
50Pa
High static pressure 4
Remote controller-less setting
Change the external static pressure setting with the DIP
switch on the P.C. board.
• Once the Set data has been changed, though it can
be to reset it to 0000 (factory default), it need
changing using remote controller (sold separately).
After setting has been completed, restart the air
conditioner.
SW501-1
SW501-2
MCU (IC501)
SW501-1
OFF
ON
OFF
ON
SW501-2
OFF
OFF
ON
ON
0000
Set data
Factory
0001
0003
0006
default
To restore the factory defaults
To return the DIP switch settings to the factory defaults,
set SW501-1 and SW501-2 to OFF, connect a
separately sold wired remote controller, and then set the
data of Code No. [5d] to "0000".
28-EN