5 AJUSTES
a) DESCRIPCIÓN
!"
RUTA: SETTINGS
SYSTEM SETUP
# TRANSFORMER
#
# GENERAL
#
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
# WINDING 1
#
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
GE Multilin
!"
TRANSFORMER
NUMBER OF WINDINGS:
2
PHASE COMPENSATION:
Internal (software)
LOAD LOSS AT RATED
LOAD:
100 kW
RATED WINDING TEMP
RISE: 65°C (oil)
NO LOAD LOSS:
10 kW
TYPE OF COOLING:
OA
TOP-OIL RISE OVER
AMBIENT:
35°C
THERMAL CAPACITY:
100.00 kWh/°C
WINDING THERMAL TIME
CONSTANT:
2.00 min
WINDING 1 SOURCE:
SRC 1
WINDING 1 RATED MVA:
100.000 MVA
WINDING 1 NOM φ-φ
VOLTAGE:
220.000 kV
WINDING 1
CONNECTION: Wye
WINDING 1 GROUNDING:
Not within zone
WINDING ~ ANGLE WRT
WINDING 1:
0.0°
WINDING 1 RESISTANCE
3φ:
10.0000 ohms
T60 relé para protección de transformador
5.3 PARÁMETROS DEL SISTEMA
Rango: 2 a 6 en pasos de 1
Rango: Internal (software), External (with CTs)
[Interno (software), Externo (con CTs)]
Rango: 1 a 20000 kW en pasos de 1
Rango: 55°C (aceite), 65°C (aceite), 80°C (seco), 115°C (seco),
150°C (seco)
Rango: 1 a 20000 kW en pasos de 1
Rango: OA, FA, Non-directed FOA/FOW, Directed FOA/FOW
Rango: 1 a 200°C en pasos de 1
Rango: 0.00 a 200.00 kWh/°C en pasos de 0.01
Rango: 0.25 a 15.00 min. en pasos de 0.01
Rango: SRC 1, SRC 2, SRC 3, SRC 4
Rango: 0.001 a 2000.000 MVA en pasos de 0.001
Rango: 0.001 a 2000.000 kV en pasos de 0.001
Rango: Wye (estrella), Delta (delta), Zig-zag (zig-zag)
Rango: Not within zone (fuera de zona),
Within zone (dentro de zona)
Rango: –359.9 a 0.0° en pasos de 0.1, («~» > 1)
(indicado cuando el devando visto no es WINDING 1)
Rango: 0.0001 a 100.0000 ohms en pasos de 0.0001
5.3.4 TRANSFORMADOR
5-43
5