5 AJUSTES
SETTING
NEUTRAL DIR OC1
FUNCTION:
Disabled=0
Enabled=1
SETTING
AND
NEUTRAL DIR OC1 BLK:
Off=0
SETTING
NEUTRAL DIR OC1
SOURCE:
NEUTRAL DIR OC1 POL
VOLT:
NEUTRAL DIR OC1 OP
CURR:
Measured VX
Calculated V_0
Zero Seq Crt (I_0)
Ground Crt (IG)
SETTING
IG
0.05 pu
NEUTRAL DIR OC1
POLARIZING:
Voltage
OR
Current
Dual
OR
NOTE:
1) CURRENT POLARIZING IS POSSIBLE ONLY IN RELAYS WITH
THE GROUND CURRENT INPUTS CONNECTED TO
AN ADEQUATE CURRENT POLARIZING SOURCE
2) GROUND CURRENT CAN NOT BE USED FOR POLARIZATION
AND OPERATION SIMULTANEOUSLY
3) POSITIVE SEQUENCE RESTRAINT IS NOT APPLIED WHEN
I
_1 IS BELOW 0.8pu
Figura 5–52: ESQUEMA LÓGICO DE SOBRECORRIENTE DIRECCIONAL DE NEUTRO
GE Multilin
SETTING
NEUTRAL DIR OC1 FWD
PICKUP:
NEUTRAL DIR OC1 OP
CURR:
RUN
3( _0 - K _1 ) PICKUP
I
I
OR
IG
PICKUP
SETTINGS
AND
NEUTRAL DIR OC1 FWD
ECA:
NEUTRAL DIR OC1 FWD
LIMIT ANGLE:
NEUTRAL DIR OC1 REV
LIMIT ANGLE:
NEUTRAL DIR OC1
OFFSET:
RUN
FWD
FWD
-3V_0
REV
3I_0
REV
Voltage Polarization
AND
RUN
FWD
Current Polarization
REV
SETTING
NEUTRAL DIR OC1 REV
PICKUP:
NEUTRAL DIR OC1 OP
CURR:
RUN
3( _0 - K _1 ) PICKUP
I
I
OR
IG
PICKUP
T60 relé para protección de transformador
5.5 ELEMENTOS AGRUPADOS
AND
OR
1.25 cy
AND
1.5 cy
OR
AND
FLEXLOGIC OPERAND
AND
NEUTRAL DIR OC1 FWD
5
FLEXLOGIC OPERAND
NEUTRAL DIR OC1 REV
827077AA.CDR