• In installing or repair, tools and components should be prevented from falling.
• Regularly check the reliability of the installation frame.
7.9 TUBING CONNECTION
• Detach the valve cover of outdoor unit.
• Align flaring nut to the thread center, and screw the nut tightly by hand.
• Screw tightly the flaring nut with torque spanner until the torque spanner produces "click" sound.
• It is recommended to use torque spanner to connect the tubing. If other flexible or fixed spanner is used,
it may damage the horn mouth due to improper force.
• The bending angle of the tube should not be too small or the tube may break up, so the service personnel
should use tube bender to bend the tube.
• Never let water, dust or sand gets into the pipe.
Thread
Wrench
Installation
support
Flaring
Pipeline
nut
Torque
wrench
Fig.11
USER AND INSTALLATION MANUAL
Fig.10
Table 2
Tubing size
(mm/inch.)
Φ6 (1/4")
Φ9.52 (3/8")
Φ12(1/2")
Φ15.88 (5/8")
Φ19.05 (3/4")
7. INSTALLATION
Torque (N.m)
15~20
35~40
50~55
60~75
80~95
65