Descargar Imprimir esta página

Airwell DVFA-140N-01M22 Manual De Operación Y Instalacion página 24

Unidad interior
Ocultar thumbs Ver también para DVFA-140N-01M22:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 103
Electrical Wiring
Indoor power supply wiring & signal wiring between indoor and outdoor & signal wiring between
indoors.
Items
Total
Current of
Indoor Units(A)
<6
≥6 and <10
≥10 and <16
≥16 and <25
≥25 and <32
• The electrical power line and signal lines must be fastened tightly.
• Every indoor unit must have the ground connection.
• The power line should be enlarged if it exceeds the permissible length.
• Shielded lays of all the indoor and outdoor units should be connected together, with the
shielded lay at the side of signal lines of outdoor units grounded at one point.
• It is not permissible if the whole length of signal line exceeds 1000m.
Signal Wiring of Wired controller
Length of Signal Line (m)
≤ 250
The shielding lay of the signal line must be grounded at one end.
The total length of the signal line shall not be more than 250m.
Rated
Cross
Length
Current of
Section
(m)
Overflow
2
(mm
)
Breaker (A)
2.5
20
4
20
6
25
8
30
10
40
Wiring Dimensions
2
0.75mm
Rated current of residual
Circuit Breaker (A)
Ground Fault
Interruptor (mA)
Response time (S)
10
10 A,30 mA,0.1S or below
16
16 A,30 mA,0.1S or below 2 coresx0.75-2.0
20
20 A,30 mA,0.1S or below
32
32 A,30 mA,0.1S or below
32
32 A,30 mA, 0.1S or below
x 3 core shielding line
16
Cross Sectional
Area of Signal Line
Outdoor-
Indoor-
indoor
indoor
2
2
(mm
)
(mm
)
2
mm
shielded lin

Publicidad

loading