Installation instructions
Dismantling
Figure
:
• Unlock and remove arresters in the manner
shown.
• Open the hat rail holder with a flat screwdriver
and engage it (see also Figure
the protection devices.
Faults
If the integrated cut-off unit trips (e.g. due to age
on account of multiple, very high overvoltages),
the visual display (Figure
greeen (grey) to red. In this case, remove the ar-
rester and insert a new arrester (available sepa-
rately, V50: item no. 5093 508, C50: item no.
5095 609). In the case of devices with multiple
arresters, it must be assumed that the other ar-
resters of this device have experienced the same
load. We recommend that you check them and, if
necessary, also replace them. Dispose of re-
placed arresters.
Remote signalling
Figure
(only V50-..+FS..):
When at least one arrester is disconnected, the
changeover contact in the remote signalling mod-
ule switches from 11/12 to 11/14. Remote signal-
ling can be switched as an NO or NC contact.
This allows control of suitable signalling compo-
nents (e.g. central error messages, light or
acoustic signal).
• Connect the remote signalling cables as
shown, in so doing maintaining the specified
cable cross-section and the stripping length.
Maintenance
We recommend carrying out a visual check of
the visual display every 2-4 years or after light-
ning strikes.
Disposal
– Packaging as household waste
– Protection device/arrester as electronic waste.
Comply with the local waste disposal regulations.
OBO Bettermann GmbH & Co. KG
Technical data
). Remove
2
U
res
) switches from
installation point
Number of Ports
Protection path
Protection path
V50 ... 320
IEC / DIN EN
Class I + II / Type 1 + 2
61643-11
U
320 V AC
C
U
230 V AC (± 10 %)
N
U
≤ 1400 V
P
900 V
1 kA
8/20
1000 V
5 kA
8/20
@
1000 V
7 kA
8/20
1100 V
12,5 kA
8/20
I
12,5 kA
T1
imp
I
30 kA
T2
n
I
50 kA
max
I
SCCR
IP code
System
TN-, TT
L – PEN
L – N
L – PE
N – PE
x
x
to metal parts/devices
F1 >160 A
gL / gG
F1
+
F2
F2 ≤ 160 A
gL / gG
F1 ≤ 160 A
F2
2
F1
gL / gG
1.5 – 35 mm
1.5 – 35 mm
1.5 – 35 mm
Accessories
a
a ≤ 15.5 mm (0.6 in)
3 x 16 mm
5012 010
V50-...-320
C50
255 V AC
≤ 1500 V
–
–
–
–
50 kA
50 kA
50 kA
50 kA
eff
IP 20 (built-in)
indoor
One-Port-SPD
TN-, TT (NPE)
-40 – +80 °C
-40 – +176 °F
5 – 95 %
N – PE
x ≥ 1,5 mm
– (NPE)
– (NPE)
(AWG 16 – 2)
2
(AWG 16 – 2)
2
(AWG 16 – 2)
2
(3 x AWG 6)
2
9
EN